Module 02 · Pre-build

Facility Energy

Define the building geometry, envelope, lighting, HVAC, and production schedule. EnergyPlus runs a full 8,760-hour simulation against TMYx weather to produce the load profile that Module 03 sizes solar & storage against.

Floor area
650
m² · two zones
Annual load
695
MWh / yr
Peak demand
142
kW · staggered
LED density
114
W/m² · 3.5 µmol/J
Envelope U
0.05
W/m²K · PUR-core
Specific energy
16.5
kWh / kg-FW basil
The staggered layout overlaps photoperiods across zones, flattening the load. Synchronized layout doubles the midday peak but shifts more energy into solar hours.

Facility geometry — 26 × 25 × 6 m

Two-zone Graamans-style indoor farm. 650 m² floor area, 6 m ceiling, closed envelope at U = 0.05 W/m²K (PUR-core sandwich). Zone A and Zone B share an interior partition. Drag to rotate, scroll to zoom.
Zone A · 325 m² · 02–20 Zone B · 325 m² · 08–02 Insulated envelope LED canopy fixtures

Monthly electricity load

Aggregated kWh per month from the 8,760-hour simulation. Slight summer rise reflects higher dehumidification load.

Mean daily load — decomposed

Average hour-by-hour breakdown across all 365 days. LED canopy dominates; HVAC adds a midday hump tracking ambient temperature.

Model inputs

The IDF file is generated by SOLARA from the geometry editor and equipment selections. Every value is auditable.
CategoryParameterValueSource
GeometryFloor area, height650 m², 6 m ceilingGeometry editor
EnvelopeU-value (all surfaces)0.05 W/m²KPUR-core sandwich panel spec
LightingLED density · efficacy114.3 W/m² · 3.5 µmol/JGraamans 2018
LightingSensible heat fraction0.48Graamans 2017
Plant modelLatent gain · transpiration65 W/m², 6-hr ramp-downGraamans plant factory model
HVACChiller COP3.7 (ideal-loads)EnergyPlus default
HVACSetpoints (occ / unocc)24 °C / 22 °CCrop spec
AtmosphereCO₂ concentration1,000 ppmProduction target
Schedule (staggered)Zone A · Zone B02–20 · 08–02Production planner
WeatherTMYx fileAgadir-Massira 602520climate.onebuilding.org

Validation

SOLARA's energy model reproduces Graamans (2018) at ≈ 235 kWh per kg lettuce dry weight versus the published 247 kWh / kg DW — within 5%. For Farm32's basil schedule (42,250 kg fresh weight per year) the specific energy is 16.5 kWh / kg-FW, below the LCA-reported 26.4 kWh / kg-FW because dehumidification overhead and capital-goods stages sit outside the EnergyPlus boundary. Those gaps close in Module 04 (Environmental Impact).

Outputs handed downstream

OutputGoes toHow it is used
8,760-hour facility load (kW)Module 03 — Solar & StorageDemand curve dispatched against PV + battery
Annual electricity consumption (MWh)Module 04 — Environmental ImpactOperational energy stage (PEFCR §5.3)
HVAC, refrigerant, LED bill of materialsModule 04 — Environmental ImpactCapital-goods stage
Design load profileOperateReal-time variance against measured kWh